TYPE
|
True three-phase transformer turns-ratio tester
|
PHYSICAL SPECIFICATIONS
|
21”W x 9”H x 17”D (53 cm x 24 cm x 43 cm); Weight: 35 lbs (15.8 Kg)
|
INPUT POWER
|
3 amps, 100 – 240 Vac, 50/60 Hz
|
MEASUREMENT METHOD
|
ANSI/IEEE C57.12.90
|
TURNS-RATIO MEASURING RANGE
|
0.8 – 15,000 (5-digit resolution)
|
TURNS-RATIO ACCURACY
|
0.8 – 999: ±0.1%, 1000 – 1599: ±0.2%, 1600 – 9999: ±1%, 10,000 – 15,000: 1.5% @ 8 Vac
0.8 – 999: ±0.1%, 1000 – 1599: ±0.2%, 1600 – 9999: ±1%, 10,000 – 15,000: 1.5% @ 40 Vac
0.8 – 999: ±0.1%, 1000 – 1599: ±0.2%, 1600 – 9999: ±1%, 10,000 – 15,000: 1.5% @ 100 Vac
|
TEST VOLTAGES
|
Three-phase, 8 Vac @ 1 Amp, 40 Vac @ 0.2 Amps, 100 Vac @ 0.1 Amp
|
EXCITATION CURRENT READING RANGE
|
0 – 1 Ampere; Accuracy: ±0.1 mA, ±2% of reading (±1 mA)
|
PHASE ANGLE MEASUREMENT
|
0 – 360 degrees; Accuracy: ± 0.2 degree (± 1 digit)
|
DISPLAY
|
Back-lit LCD screen (64 x 128 dot graphic display); Viewable in bright sunlight and low-light levels
|
PRINTER
|
Built-in 4.5-inch wide thermal printer
|
EXTERNAL DATA STORAGE
|
One USB Flash drive interface port; Up to 999 transformer test records can be stored on a USB Flash drive (not included).
|
COMPUTER INTERFACES
|
One RS-232C port, One USB port
|
PC SOFTWARE
|
Windows? XP/Vista-based Transformer Turns-Ratio Analyzer application is included with purchase price
|
INTERNAL TEST RECORD STORAGE
|
Stores up to 112 transformer test records. Each record holds the test record header and up to 33 readings.
|
INTERNAL TEST PLAN STORAGE
|
Stores up to 128 transformer test plans. Test plans can be transferred to the unit from the PC via the RS-232C/USB port or via the USB Flash drive interface
|
LOAD TAP CHANGER CONTACT
|
240 Vac, 1 Amp
|
SAFETY
|
Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards
|
ENVIRONMENT
|
Operating: -10° to 50° C (15°F to +122° F); Storage: -30° C to 70° C (-22°F to +158° F)
|
CABLES
|
One 15-foot single-phase set, One 15-foot three-phase set, One 25- foot extension set, One ground cable, One USB cable, One RS-232C cable, power cord, cable bag
|
OPTIONS
|
Transportation case
|
WARRANTY
|
One year on parts and labor
|
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
|