美国vanguard ATRT-03 S2三相变压器线圈匝数比测试仪
美国vanguard ATRT-03 S2三相变压器线圈匝数比测试仪
产品价格:(人民币)
  • 规格:ATRT-03 S2
  • 发货地:上海
  • 品牌:
  • 最小起订量:1件
  • 诚信商家
    会员级别:钻石会员
    认证类型:企业认证
    企业证件:通过认证

    商铺名称:上海山合海融商贸有限公司

    联系人:孙宝金(先生)

    联系手机:

    固定电话:

    企业邮箱:sh@51082245.com

    联系地址:上海市宝山区陆翔路678弄60号

    邮编:201907

    联系我时,请说是在智能安防网上看到的,谢谢!

    商品详情

      The Vanguard Instruments ATRT-03 S2 is the third generation, microprocessor-based, automatic, three phase, transformer turns-ratio tester. This light weight, rugged, portable unit is designed for transformer testing at utility power substations.

      The ATRT-03 S2 determines the transformer turns ratio using the IEEE C57.12.90 measurement method. The ATRT-03 S2 outputs an excitation test voltage to the transformer primary windings. The induced secondary voltage is sensed and the transformer turns ratio is calculated. The ATRT-03 S2 is capable of measuring turns ratios from 0.8 to 15,000. The transformer turns-ratio, excitation current, and phase angle readings are displayed on the large LCD. The automatic transformer type detection feature allows the ATRT-03 S2 to detect and test 130 transformer types defined by ANSI, CEI/IEC and Australian standards.


      • Highest ratio: 0.8 - 15,000
      • Capable of detecting 130 different 3-phase transformer types defined by ANSI, IEC, and Australian standards
      • 3 Test voltages available: 8Vac, 40Vac, 100Vac
      • Phase angle and excitation current measuring
      • Computer Interface (RS-232C and USB Port)
      • USB flash drive interface
      • Name-plate turns ratio calculation
      • Computed % error based on measured and calculated ratio
      • Optional 4.5" thermal printer
      • Powered from a single phase 100-264 Vac 50/60 Hz

      ATRT-03 S2

      Cables

       
             
             

      ATRT-03 S2

      Technical Specifications

       
             
      TYPE Portable, lightweight, automatic, 3-phase transformer turns-ratio meter
      PHYSICAL SPECIFICATIONS 18”W x 7”H x 15”D   (45.7 cm x 17.8 cm x 38.1 cm); Weight: 20 lbs (9.0 kg)
      OPERATING VOLTAGE 100 – 240 Vac, 50/60 Hz
      MEASUREMENT METHOD ANSI/IEEE C57.12.90
      TURNS-RATIO MEASURING RANGE 0.8 – 15,000

      TURNS-RATIO ACCURACY

      0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.25%. 4,000 – 15,000: ±1% @ 8 Vac
      0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.20%. 4,000 – 15,000: ±1% @ 40 Vac
      0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.15%. 4,000 – 15,000: ±1% @ 100 Vac
      TEST VOLTAGES 8 Vac @ 1Amp, 40 Vac @ 0.2 Amp, 100 Vac @ 0.1 Amp
      EXCITATION CURRENT READING RANGE 0 – 1 Ampere; Accuracy: ±0.1 mA, ±2% of reading (±1 mA)
      PHASE-ANGLE MEASUREMENT

      0 – 360 Degrees; Accuracy: ±0.2 degree (±1 digit)

      DISPLAY Back-lit LCD screen (64 x 128 dot graphic display); Viewable in bright sunlight and low-light levels
      PRINTER Built-in 4.5-inch wide thermal printer (Optional)
      COMPUTER INTERFACES One RS-232C port, One USB port
      EXTERNAL DATA STORAGE One USB Flash drive interface port; Up to 999 transformer test records can be stored on a USB Flash drive (not included).
      PC SOFTWARE Windows? XP/Vista-based Transformer Turns-Ratio Analyzer application is included with purchase price
      INTERNAL TEST RECORD STORAGE
      stores 112 complete transformer test records, each record holding the test
      record header and up to 99 readings
      INTERNAL TEST PLAN STORAGE

      Can store 128 transformer test plans internally. Test plans can be transferred to the unit from the PC via the RS-232C/USB port or via the USB Flash drive interface

      LOAD TAP CHANGER CONTACT 240 Vac, 2 Amps
      SAFETY Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards
      ENVIRONMENT Operating: -10? to 50? C (15? to +122? F); Storage: -30? C to 70? C (-22? to +158? F)
      CABLES One 15-foot Single-phase set, One 15-foot 3-phase set, One 25-foot extension set, One safety ground, One USB, One RS-232C, cable bag
      OPTIONS Transportation Case
      WARRANTY One year on parts and labor
      Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).

    在线询盘/留言
  • 0571-87774297