商铺名称:上海山合海融商贸有限公司
联系人:孙宝金(先生)
联系手机:
固定电话:
企业邮箱:sh@51082245.com
联系地址:上海市宝山区陆翔路678弄60号
邮编:201907
联系我时,请说是在智能安防网上看到的,谢谢!
The ATRT-01 S3 is Vanguard’s fourth generation, micro-processor based, single phase, automatic transformer turns-ratio tester. The ATRT-01 S3 uses the IEEE C57.12.90 measuring method to determine the transformer turns-ratio. The transformer turns-ratio is determined by precisely measuring the voltages across the unloaded transformer windings. The ATRT-01 S3’s measuring circuitry self adjusts before each measurement to ensure turns-ratio accuracy. Two selectable test voltages, 4Vac and 40Vac, offer flexibility in testing different types of transformers.
ATRT-01 S3
Cables
Cable
Part Number
[8000-0006] RS-232C Cable [ 6' (1.83m) ]
8000-0006
[8000-0093] H and X Cable Set [ 15' (4.57m) ]
8000-0093
[8000-0112] Power Cable
8000-0112
ATRT-01 S3
Technical Specifications
TYPE
Transformer Turns Ratio Tester
PHYSICAL SPECIFICATIONS
Dimensions: 12” x 10” x 8” (30.4 cm x 25.4 cm x 20.3 cm)
Weight: 8 lbs. (3.6 Kg)
INPUT POWER
120 or 240 Vac (Selectable), 50/60 Hz
MEASURING METHOD
ANSI/IEEE C57.12.90
RATIO MEASURING RANGE
0.8 - 15,000 (5 digit resolution)
TURNS-RATIO ACCURACY
40 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (1%)
4 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (2%)
TEST VOLTAGE
4 Vac @ 1.0A, 40 Vac @ 0.6A
PHASE ANGLE MEASUREMENT
0 - 360 degrees, Accuracy ±0.2 degree (±1 digit)
POLARITY READING
In-Phase or Out-of-Phase indication
EXCITATION CURRENT READING RANGE
0-2 Amperes, Accuracy: 2% of reading (±1 mA)
DISPLAY
Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels
COMPUTER INTERFACE
RS-232C
PC SOFTWARE
Windows XP/Vista/7 Transformer Analysis Software (included with purchase)
INTERNAL TEST RECORD STORAGE
128 records of 33 readings
EXTERNAL TEST RECORD STORAGE
Up to 999 test records on external USB Flash drive.
SAFETY
Designed to meet IEC 61010 (1995), UL 61010A-1, and CSA-C22.2 standards
ENVIRONMENT
Operating: -10oC to 50oC (15oF to +122oF)
Storage: (-30oC to 70oC (-22oF to +158oF)
HUMIDITY (MAX)
90% RH @ 40? C (104? F) non-condensing
ALTITUDE (MAX)
2000m (6562 ft) to full safety specifications
CABLES
One 15 ft. (4.6m) Single phase cable, one power cord, one cable bag
OPTIONS
Transportation Case (Can hold unit and cables)
WARRANTY
One year on parts and labor