The RFD-200 S3 is a portable relay test set that delivers performance verification testing of electromechanical, electronic, and microprocessor-based protective relays in their operating installations. The RFD-200 S3 is a rugged test set suitable for testing a variety of protection relays operated in both indoor and outdoor environments. The unit’s ergonomic design and intuitive control panel layout make it ideal for first-time users who have little or no training.
RFD-200 S3
Cables
Cable
Part Number
[8000-0016] Power + Ground Combination Cable
8000-0016
[8000-0078] RFD-200 Cable Set
8000-0078
RFD-200 S3
Technical Specifications
TYPE
Portable relay test set
INPUT POWER
100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz
PHYSICAL SPECIFICATIONS
17”W x 12.5”H x 12”D, (42.7 cm x 32.0 cm x 30.5 cm); Weight: 35 lbs (15.9 kg)
AMPERE METER INPUT RANGES
Internal input range: 0 – 250 A; Accuracy: 2% of reading ± 10 mA,
External AC input range: 0 – 6A; Accuracy: 1% of reading ± 10mA
External DC input range: 0 – 6A; Accuracy: 0.5% of reading ±1 count
Measurement Method: True RMS for AC
VOLT METER INPUT RANGE
0 – 600.0V; AC accuracy: 1% of reading ±1 count; DC accuracy 0.5% of reading ±1 count
Measurement Method: True RMS for AC
AUXILIARY POWER SUPPLIES
24 Vdc @ 1 A, 48 Vdc @ 0.25 A, 124 Vdc @ 0.125 A
POWER RESISTORS
5 Ω/50 W, 1 Ω/50 W, 25 Ω/50 W, 100 Ω/50 W, 500 Ω/50 W
SAFETY
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
ENVIRONMENT
Operating: -10?C to 50? C (15?F to +122? F); Storage: -30? C to 70? C (-22?F to +158? F)
OPTIONS
Transportation case
WARRANTY
One year on parts and labor
AC Current Output
Range
No-Load Voltage
Load Voltage
Load Current
Load/Unload Times
10 A
90 Vac
75 Vac
10 A
2 min / 15 min
40 A
25 Vac
20 Vac
40 A
1 min / 15 min
100 A
10 Vac
7.25 Vac
100 A
1 min / 15 min
100 A
10 Vac
3 Vac
250 A
1 sec / 5 min
AC Voltage Output
Range
No-Load Voltage
Load Voltage
Load Current
Load/Unload Times
250 Vac
260 Vac
240 Vac
3 A
10 min / 45 min
DC Voltage Output
Range
No-Load Voltage
Load Voltage
Load Current
Load/Unload Times
300 Vdc
300 Vdc
250 Vdc
2 A
10 min / 45 min
RFD-200 Timer Second Display In seconds and cycles (50/60 Hz programmable)
Range
Resolution
Accuracy
0 to 9.999 sec
1 ms
± (1 ms + 0.01%)
10.00 to 99.99 sec
10 ms
± (10 ms + 0.01%)
100.0 to 999.999 sec
100 ms
± (100 ms + 0.01%)
Timer Cycles Display
Range
Resolution
Accuracy
0 to 9.999 cycles
0.1 cycle
± (0.1 cycle + 0.01%)
1,000 to 49,999 cycles / 50 Hz
1 cycle
± (1 cycle + 0.01%)
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).