      The CT-8000 S3 is Vanguard's fourth generation EHV circuit breaker analyzer. The CT-8000 S3 is available with 3 (part number 9103-UC) or 6 contact timing channels (part number 9104-UC). The CT-8000 S3 can fully analyze a circuit breaker's performance by measuring the main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes. Also, an outstanding feature of the CT-8000 S3 is the ability to perform dynamic resistance tests on circuit breaker contacts.


      • Fully analyze circuit breaker's performance by measuring main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes
      • Perform dynamic contact resistance test
      • USB computer interface
      • USB Flash drive interface (Flash drive not included)
      • Store up to 200 test records and 100 test plans internally
      • Initiate Breaker Operation
      • Built-in 4.5" wide Thermal Printer
      • Rugged "QWERTY" style membrane keypad
      • Optional "On-line" Timing Mode
      • Optional dual ground testing mode
      • Optional Bluetooth wireless computer interface

      CT-8000 S3

      Cables

       
             
             

      CT-8000 S3

      Technical Specifications

       
             
      TYPE Portable circuit-breaker analyzer
      PHYSICAL SPECIFICATIONS 16”W x 11”H x 14”D (40.6 cm x 29.9 cm x 35.6 cm); Weight: 22 lbs (9.98 kg)
      INPUT POWER 100-240Vac, 10A, 50/60Hz
      DRY-CONTACT INPUTS 3 channels (9103-UC) or 6 channels (9104-UC). Channel can detect the main contact and resistor contact time.
      TIMING WINDOWS 1 second, 10 seconds, or 20 seconds
      TIMING RESOLUTIONS ±50 micro-seconds @ 1 sec. duration,
      ±500 micro-seconds @ 10 sec. duration,
      ±1.0 milli-seconds @ 20 sec. duration
      TIMING ACCURACY 0.05% of reading ±0.05 ms @ 1 second duration
      DRY-CONTACT CHANNEL PROTECTION All contact inputs are grounded until test. Input channels are also protected against static discharge.
      DRY-CONTACT DETECTION RANGE Closed: Less than 20 Ohm. Opened: greater than 5000 ohm
      INSERTION RESISTOR DETECTION RANGE 50 - 5,000 ohms
      TRIGGER INPUT VOLTAGE Open/Close trigger voltage: 24 V – 300V DC or peak AC
      VOLTAGE SENSING INPUT RANGE V1: analog input; 0 – 250 V DC or peak AC; sensitivity ±1 V; record and print voltage level
      V2 and V3: voltage presence/absence detector input; 24 – 255 V DC or peak AC; record and print 3 timing events
      BREAKER OPERATIONS Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
      BREAKER INITIATE CAPACITY 30A, 250 Vac/dc max
      INITIATE CURRENT READING RANGE one, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5 Khz AC
      DIGITAL TRAVEL TRANSDUCER INPUTS 3 digital travel transducer channels; linear range: 0.0 – 60.0 in (±0.01 in)
      rotary range: 0 – 360 degrees (±0.36 degrees)
      RESISTOR TYPE TRANSDUCER INPUTS 3 channels, 200 ohm – 10K ohms
      CONTACT TRAVEL POINT DIFFERENCE measures “slow-close” contact-point distances; results can be printed
      DYNAMIC/STATIC RESISTANCE RANGE 0.1 – 1,999 micro-ohms; accuracy: ±2% of reading, ±5 micro-ohms
      RESISTANCE TEST CURRENT 200 amperes max
      DISPLAY back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light
      PRINTER built-in 4.5” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results
      INTERNAL TEST RECORD STORAGE Store upt to 200 test records and 100 test plans
      EXTERNAL TEST RECORD STORAGE USB Flash drive interface for external storage of test records and test plans
      COMPUTER INTERFACES One USB port, optional Bluetooth wireless interface
      PC SOFTWARE Windows? based Breaker Analysis software included with purchase price
      CABLES furnished with full set of test leads
      OPTIONS transportation cases (available for the CT-8000 S3 and travel transducers), on-line timing mode, dual ground testing mode,
      bluetooth interface
      SAFETY designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
      ENVIRONMENT Operating: -10°C to +50°C (+15°F to +122°F);
      Storage: -30°C to +70°C (-22°F to +158°F)
      HUMIDITY 90% RH @ 40°C (104°F) non-condensing
      ALTITUDE 2,000 m (6,562 ft) to full safety specifi cations
      WARRANTY one year on parts and labor
      Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).

       

      OPTIONAL TESTING FEATURES
        ON-LINE TIMING MODE
      ON-LINE CURRENT SENSOR three non-contact AC current sensors, range 0-100 amperes
      ON-LINE DC CURRENT SENSOR one non-contact DC current sensor, range 0-20 amperes
        DUAL GROUND TIMING MODE
      DUAL GROUND CLAMP-ON PROBES 3 non-contact clamp-on probes