The CT-8000 S3 is Vanguard's fourth generation EHV circuit breaker analyzer. The CT-8000 S3 is available with 3 (part number 9103-UC) or 6 contact timing channels (part number 9104-UC). The CT-8000 S3 can fully analyze a circuit breaker's performance by measuring the main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes. Also, an outstanding feature of the CT-8000 S3 is the ability to perform dynamic resistance tests on circuit breaker contacts.
CT-8000 S3
Cables
Cable
Part Number
[8000-0005] USB Cable [ 6' (1.83m) ]
8000-0005
[8000-0016] Power + Ground Combination Cable
8000-0016
[8000-0097] Contact Extension Cable [ 30' (9.14m) ]
8000-0097
[8000-0099] Initiate Cable [ 22' (6.71m) ]
8000-0099
[8000-0101] Test Lead (Trigger, V1, V2) [ 2' (0.61m) ]
8000-0101
[8000-0102] Analog Transducer Cable
8000-0102
[8000-0104] Transducer Cable [ 25' (7.62m) ]
8000-0104
[8000-0174] CT-7000 S3/8000 S3 Contact Cable (4 pin, 20')
8000-0174
[8000-0175] CT-7000 S3/8000 S3 Contact Extension Cable (4 pin, 30')
8000-0175
[8000-0213] CT-8000 S3 Current/Sense Cable Set
8000-0213
CT-8000 S3
Technical Specifications
TYPE
Portable circuit-breaker analyzer
PHYSICAL SPECIFICATIONS
16”W x 11”H x 14”D (40.6 cm x 29.9 cm x 35.6 cm); Weight: 22 lbs (9.98 kg)
INPUT POWER
100-240Vac, 10A, 50/60Hz
DRY-CONTACT INPUTS
3 channels (9103-UC) or 6 channels (9104-UC). Channel can detect the main contact and resistor contact time.
TIMING WINDOWS
1 second, 10 seconds, or 20 seconds
TIMING RESOLUTIONS
±50 micro-seconds @ 1 sec. duration,
±500 micro-seconds @ 10 sec. duration,
±1.0 milli-seconds @ 20 sec. duration
TIMING ACCURACY
0.05% of reading ±0.05 ms @ 1 second duration
DRY-CONTACT CHANNEL PROTECTION
All contact inputs are grounded until test. Input channels are also protected against static discharge.
DRY-CONTACT DETECTION RANGE
Closed: Less than 20 Ohm. Opened: greater than 5000 ohm
INSERTION RESISTOR DETECTION RANGE
50 - 5,000 ohms
TRIGGER INPUT VOLTAGE
Open/Close trigger voltage: 24 V – 300V DC or peak AC
VOLTAGE SENSING INPUT RANGE
V1: analog input; 0 – 250 V DC or peak AC; sensitivity ±1 V; record and print voltage level
V2 and V3: voltage presence/absence detector input; 24 – 255 V DC or peak AC; record and print 3 timing events
BREAKER OPERATIONS
Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
BREAKER INITIATE CAPACITY
30A, 250 Vac/dc max
INITIATE CURRENT READING RANGE
one, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5 Khz AC
DIGITAL TRAVEL TRANSDUCER INPUTS
3 digital travel transducer channels; linear range: 0.0 – 60.0 in (±0.01 in)
rotary range: 0 – 360 degrees (±0.36 degrees)
RESISTOR TYPE TRANSDUCER INPUTS
3 channels, 200 ohm – 10K ohms
CONTACT TRAVEL POINT DIFFERENCE
measures “slow-close” contact-point distances; results can be printed
DYNAMIC/STATIC RESISTANCE RANGE
0.1 – 1,999 micro-ohms; accuracy: ±2% of reading, ±5 micro-ohms
RESISTANCE TEST CURRENT
200 amperes max
DISPLAY
back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light
PRINTER
built-in 4.5” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results
INTERNAL TEST RECORD STORAGE
Store upt to 200 test records and 100 test plans
EXTERNAL TEST RECORD STORAGE
USB Flash drive interface for external storage of test records and test plans
COMPUTER INTERFACES
One USB port, optional Bluetooth wireless interface
PC SOFTWARE
Windows? based Breaker Analysis software included with purchase price
CABLES
furnished with full set of test leads
OPTIONS
transportation cases (available for the CT-8000 S3 and travel transducers), on-line timing mode, dual ground testing mode,
bluetooth interface
SAFETY
designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
ENVIRONMENT
Operating: -10°C to +50°C (+15°F to +122°F);
Storage: -30°C to +70°C (-22°F to +158°F)
HUMIDITY
90% RH @ 40°C (104°F) non-condensing
ALTITUDE
2,000 m (6,562 ft) to full safety specifi cations
WARRANTY
one year on parts and labor
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
OPTIONAL TESTING FEATURES
ON-LINE TIMING MODE
ON-LINE CURRENT SENSOR
three non-contact AC current sensors, range 0-100 amperes
ON-LINE DC CURRENT SENSOR
one non-contact DC current sensor, range 0-20 amperes
DUAL GROUND TIMING MODE
DUAL GROUND CLAMP-ON PROBES
3 non-contact clamp-on probes