DigiTMR S2
EHV Circuit Breaker Analyzer
The Vanguard DIGITMR S2 is an inexpensive, easy to use digital circuit breaker analyzer. The DIGITMR S2 can be operated stand-alone or can be computer-controlled. It can fully analyze a circuit-breaker’s performance by testing the contact time, stroke, velocity, over-travel, and contact wipe. Contact and motion analysis can be performed for all breaker contact operations (Open, Close, Open – Close, Close – Open, and Open – Close – Open). Timing results are recorded and displayed on the 240 x 128 pixels back-lit LCD screen and can also be printed on the built-in 4.5" wide thermal printer.
DigiTMR S2
Cables
Cable
Part Number
[8000-0005] USB Cable [ 6' (1.83m) ]
8000-0005
[8000-0016] Power + Ground Combination Cable
8000-0016
[8000-0095] Contact Extension Cable [ 30' (9.14m) ]
8000-0095
[8000-0096] Contact Test Lead [ 20' (6.10m) ]
8000-0096
[8000-0097] Contact Extension Cable [ 30' (9.14m) ]
8000-0097
[8000-0099] Initiate Cable [ 22' (6.71m) ]
8000-0099
[8000-0101] Test Lead (Trigger, V1, V2) [ 2' (0.61m) ]
8000-0101
[8000-0104] Transducer Cable [ 25' (7.62m) ]
8000-0104
DigiTMR S2
Technical Specifications
TYPE
portable digital circuit breaker analyzer
PHYSICAL SPECIFICATIONS
18.5”W x 14”H x 7”D (47.0 cm x 35.7 cm x 17.6 cm);
Weight: 20 lbs (9.1 kg)
INPUT POWER
3 Amps, 100 – 240 Vac, 50/60 Hz
DRY-CONTACT INPUTS
3 dry-contact channels; each channel detects main contact and insertion resistor contact
TIMING WINDOWS
1-second, 10-seconds, or 20-seconds
TIMING RESOLUTIONS
±50 micro-seconds @ 1-second duration, ±500 micro-seconds @ 10-second duration, ±1.00 milli-second @ 20-second duration
TIMING ACCURACY
0.05% of reading ±0.1 ms @ 1-second duration
CONTACT DETECTION RANGE
Closed: less than 20 ohms; Open: greater than 5,000 ohm
RESISTOR DETECTION RANGE
50 – 5,000 ohms
TRIGGER INPUT VOLTAGE
Open/Close: 30 – 300V, DC or peak AC
VOLTAGE SENSING INPUT RANGE
V1: analog input; 0 – 255V, DC or peak AC; Sensitivity: ±1V
V2: voltage presence/absence detector input; 30 – 300V, DC or peak AC
BREAKER OPERATIONS
Initiate Open, Close, Open – Close, Close – Open, Open – Close – Open
BREAKER INITIATE CAPACITY
30A, 250 Vac/dc max
INITIATE CURRENT READING RANGE
One, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5Khz
TRAVEL TRANSDUCER INPUT
1 digital travel transducer channel; Linear range: 0.0 – 60.0 in (±0.005 in.); Rotary range: 0 – 360 degrees (±0.006 degrees)
CONTACT TRAVEL POINT DIFFERENCE
Measures “slow-close” contact-point distances; results can be printed
CT CURRENT SENSOR
One, non-contact, 0 – 100A
DISPLAY
Back-lit LCD screen (240 x 128 pixels); viewable in bright sunlight and low light levels
PRINTER
Built-in 4.5-inch wide thermal printer can print both graphic contact travel waveforms and tabulated test results
INTERNAL TEST RECORD STORAGE
Stores up to 200 test records and 100 test plans
COMPUTER INTERFACES
One USB port, optional Bluetooth interface
PC SOFTWARE
Windows?-based Vanguard Circuit Breaker Analysis (VCBA S2) software is included with purchase price. Software updates available at no additional charge.
SAFETY
Designed to meet UL/IEC 61010 and CAN/CSA C22.2 No. 1010.1-92 standards
ENVIRONMENT
Operating: -10°C to 50° C (15°F to +122° F); Storage: -30° C to 70° C (-22°F to +158° F)
OPTIONS
Transportation case (available for the DigiTMR S2 and the travel transducers)
WARRANTY
One year on parts and labor