controller setpoint value
End On: Final value or controller setpoint
Guaranteed Soak: Off, below setpoint only, above setpoint
only or above and below setpoint. On
ramps only, on soaks only or on both
ramps and soaks. Guaranteed Soak band
may be set from 0 to input span.
Timebase: Either hours:minutes or minutes:seconds
(x60); x60 pre-programmable or may be
set during Program Run.
Segment Time: May be set in the range 0 to 99:59
(hours:minutes or minutes:seconds)
Ramp Rate: 0 to 9999 least significant digits per hour or
minute
END OF PRO GRAM OUT PUT
Type: Relay
Contact Type: Single pole, double throw (SPDT Form C)
Rating: 5A resistive @ 120/240V AC
Lifetime: >100,000 operations @ rated
voltage/current
Isolation: Inherent
EVENT OUT PUTS - OP TION
Type: Relay (4)
Contact Type: Single pole, single throw; normally open.
Rating: 5A resistive @ 120/240V AC
B-7Lifetime: > 100,000 operations @ rated
voltage/current
Isolation: Inherent
Programmability: Each event is programmable to either OFF
or ON for each segment.
DIGI TAL (RE MOTE PRO GRAM CON TROL) IN PUTS - OP TION
Type: Voltage- free con tact and TTL- compatible
Number available: Six: (a) Run/Hold, x60, Abort (b) Three
(binary-coded) Program Select
Active State: Max. Contact Resistance (Closed) = 50W
Max. Voltage (TTL) for “0" = 0.8V
Min. Voltage for ”0" = –0.6V
Non-Active State: Min. Contact Resistance (Open) = 5,000W
Min. Voltage (TTL) for “1" = 2.0V
Max. Voltage for ”1" = 24.0V
Max. Input Delay (OFF -
ON):
0.25 seconds
Min. Input Delay (ON -
|