详细介绍:
DC1030CL-301000-E
联系人:魏工 电话:15882174684
座机:028-84472033
QQ:2030149354
产品资料:
power-up, hold down the Up and SET UP keys simultaneously for
approximately five seconds. NOTE: This must be the first key action after
power-up.
The Digital Controller Programmer will then enter Configuration Mode, whereupon
the upper and lower main displays will initially be of the form:
showing the current input code selected, and the Message Display will show:
The user may then step through the Configuration Mode parameters using the
SET UP key. For each parameter, the Message Display will show a legend
identifying that parameter and the lower main display will show the current
parameter setting. The setting may be adjusted using the Up/Down keys. As soon
as the setting is changed, the lower main display will flash, indicating that the new
setting has yet to be confirmed. When the setting is as required, it may be
confirmed by pressing the MODE key, whereupon the upper display will become
static.
NOTE: Changes to the setting of certain Configuration Mode parameters
(e.g. input range, output use and type) will cause the Program Define
Mode and Controller Define Mode parameters to be automatically set to
their default values.
4-14.2 HARDWARE DEFINITION CODE
This parameter is a special facility in Configuration Mode, which is used to specify
the hardware fitted (input type, output types etc.); this must be compatible with
the hardware actually fitted. It can be accessed, with the Digital Controller
Programmer in Configuration Mode, by simultaneously pressing the Down and
SET UP keys. The Message Display will then show:
and the lower main display will be of the form:
The displayed code may be incremented/decremented using the Up/Down keys
as required. The maximum setting available for this code is 4777. For example,
the code for a thermocouple input, DC 4 - 20mA primary output (Output 1) and
relay Output 3 would be 2701. When the code is first altered, the code display will
flash, until the desired value is displayed and confirmed by pressing the MODE
key.
NOTE: It is essential that this code is changed promptly whenever there is a
change to the Digital Controller Programmer’s hardware configuration
(change of input/output type, alarm/recorder output added/removed etc.).
The Digital Controller Programmer software depends upon this code to
operate correctly.
Hardware Definitions may be viewed as Read Only displays in Base Mode by
pressing the SET UP and Down keys simultaneously.
Whilst the Hardware Definition Code is displayed, pressing the SET UP key will
cause the Message Display to change to:
and the lower main dis play to change to one of:
The desired setting can be achieved using the Up/Down keys. Pressing the SET
UP key will change the Message Display to:
and the lower main display to one of:
|